ELECTRICAL WORKS
A. METHOD OF CONDUITING, BOX FIXING & INTERNAL WIRING
1. Carry out the work as per the latest approved drawings confirmed by the concerned Project Engineer. All electrical conductors shall be of sufficient size and current rating for the purposes for which they are to be used.
2. Use medium /heavy gauge rigid PVC Conduit: 20 /25 /32 mm diameter, 2mm thick black colour and of ISI approved make, as indicated in drawing.
3. Conduits should be laid between the reinforcement of slab and properly fastened to the reinforcement with binding wires.
4. Care should be taken to see that the conduits are held in position and the cement grout does not enter the conduits while concreting and no conduits get damaged due to movement of laborers on the slab before pouring and during pouring for inspection of conduits & joints. For the floor conduiting care should be taken that conduiting is done only just before the flooring works starts.
5. Vertical conduits in wall chase to be properly fixed in position at the location indicated in the drawing. Horizontal runs of conduits in wall to be avoided as far as possible. In hollow blocks, horizontal chases are not permitted.
6. Bends in conduit pipes should not be sharp. In embedded conduiting bends made with bending spring with large radius should be used. The maximum bending radius allowed in any conduit is 2.5 times the diameter of the conduit. The use of readymade bends should be avoided as far as possible.
7. Switch boxes to be recessed in the wall in such a way that it should be projecting 1-3 mm from wall plaster. The thickness of plaster shall be ascertained with button or bull marks and confirmed by site engineer. The boxes may project a maximum of 1-3 mm. Further, the wall finish such as lime rendering or punning, Glazed Tiles / Marble / Granite, etc. are to be confirmed with concerned Project Engineer. The finish will determine the projection. The idea is to ensure the box projects 0.5mm beyond the painted surface and the edges do not break while the wire is drawn.
8. Cover all the boxes with thermocol and masking tape / dummy plates to avoid damages during plastering. These covers should be removed only at the time of wiring.
9. Pass GI pull wires of 16-gauge inside the conduits with additional loop length of 15cm as draw wire.
10. The wiring cables to be of ISI approved make, PVC insulated, stranded copper and 1100V grade. Use following cross section for wiring.
6 Sqmm - Sub mains (or as per drawing)
4 Sqmm - Power Circuit
2.5 Sqmm - Lighting Circuit
Earthing for Sub mains
1.5 Sqmm - Light point wiring, 5A socket outlets & fan circuits
Earthing for Power Circuits
1 Sqmm - Earthing for light point wiring, 5A socket outlets & Fan Circuits.
11. Red, Yellow, and Blue for phases, Black for Neutral and Green for earth – colour coding for wires must be followed.
12. Expansion coupler shall be used when conduit passes through building expansion joint. One end of the expansion coupler shall not be glued.
13. Earthing
At every light point earthing terminal should be provided and connected to the earth continuity conductor. The resistance of any point of the earth continuity system to the main earth electrode should not be more than 0.5 ohm.
Every electrical circuit and sub-circuit shall be protected against excess current by circuit breakers. No circuit breaker other than a linked circuit breaker shall be inserted in a conductor connected with earth.
Where metal works other than current carrying conductors is liable to become charged with electricity, the metal works shall be earthed in such a manner as to ensure immediate electrical discharge without danger. The neutral conductor shall be insulated throughout and at no point it should be connected to the earthing system.
All earth connections shall be visible for inspection and shall be carefully made; if they are poorly made or inadequate for the purpose for which they are intended, loss of life and property or serious personal injury may result.
Joints in the earthing should be invariably done by means of welding except in such locations where intermittent disconnection of joints is necessitated for testing purpose or for the earthing connection to the body of the equipment etc.
Use fully insulated tools while handling electric wires and equipment.
14. Mounting Height of Electrical Accessories
Light switch - 1250 mm above Finished Floor Level (F.F.L.)
Bell Push - 1250 mm above Finished Floor Level (F.F.L.)
Socket Outlet - 300 mm above Finished Floor Level (F.F.L.)
TV/Telephone Outlets - 300 mm above Finished Floor Level (F.F.L.)
Bedside Accessories - 600 mm above Finished Floor Level (F.F.L.)
Socket Outlets in the Kitchen- 1140 mm above Finished Floor Level (F.F.L.) and (+300mm from Counter Top)
Cooker Control unit 1140 mm above Finished Floor Level (F.F.L.) and (+300mm from Counter Top)
Wall Lights - 2200 mm above Finished Floor Level (F.F.L.)
15 A in Utility for Washing Machine 900 mm above Finished Floor Level (F.F.L.)
Connection Unit for Exhaust Fan 2300 mm above Finished Floor Level (F.F.L.)
EXTERNAL CABLE LAYING
Cable laying involves two steps
Trenching.
Cable Pulling / Laying.
TRENCHING
Trenches are dug as per requirement of cable sizes and other atmospheric conditions before digging route has to be finalized. The areas to be avoided for cable laying are near sewage line, Ground-containing ashes, Slag, Clinker, Fertilized Solid & Electrolytic Corrosion, which will affect the life of cables.
Standard Depth of Trenches:
Up to 1.1 KV = 450 to 750mm.
Up to 11KV =750 to 900mm.
CABLE LAYING
Before laying the direction in which the cable is to be pulled should first be decided. If it is a new cable no special precautions are necessary, but if it is laying parallel to the existing cable, the core sequence to be synchronized. Pulling force for Copper & Aluminium cables with steel tape armour when pulled is as follows:
Copper - 7 Kg /Sqmm of total conductor area
Aluminium - 2 Kg /sqmm of total conductor area
Also bending radius should be taken in to consideration.
Rating |
Single-Core Unarmoured |
Multi-Core armoured |
Up to 11KV |
15 D |
12 D |
Up to 22KV |
20 D |
15 D |
Up to 33KV |
25 D |
20 D |
I |
Hand
Tools |
|
|
|
|
1 |
Screw
Drivers - Flat |
Small,
Medium & Heavy Duty |
2 |
Screw
Drivers - Star |
Small,
Medium & Heavy Duty |
3 |
Cutting
Pliers |
Small,
Medium & Heavy Duty |
4 |
Nose
Pliers |
|
5 |
Wire
Stripper |
|
6 |
Line
Tester |
|
7 |
Hammer |
Small,
Medium & Heavy Duty |
8 |
Chisel |
|
9 |
File |
Rough,
Smooth |
10 |
Hacksaw
Frame |
|
11 |
Hacksaw
Blade |
Ordinary,
High Speed |
12 |
Ring
Spanner Set |
|
13 |
Box
Spanner set |
|
14 |
Metal
Tool Box |
|
15 |
Crimping
Tools |
Small,
Medium & Heavy Duty |
16 |
Telephone
Crimping tool |
|
17 |
Hole
saw Cutter |
|
18 |
Bending
Spring |
20
mm & 25 mm |
19 |
Curtain
Spring |
|
20 |
Line
Dori |
|
21 |
Blow
Lamp |
|
|
|
|
II |
Power
Tools |
|
|
|
|
1 |
Hammer
Drilling Machine |
|
2 |
Air
Blowing Machine |
|
3 |
Angle
Grinding Machine |
|
4 |
Mini
Drilling Machine |
|
5 |
Hammer
Drill Bits |
Different
Sizes |
6 |
DC
Segmented/Non-Segmented Blades |
|
|
|
|
III |
Measuring
Instruments |
|
|
|
|
1 |
Multimeter |
|
2 |
Digital
Clamp Meter (Tong Tester) |
|
3 |
Megger |
|
4 |
Earth
Resistance Tester |
|
5 |
Lux
Meter |
|
6 |
Measuring
Tapes |
Different
Lengths |
7 |
Spirit
Level |
Different
Lengths |
No comments:
Post a Comment